function
error or malfunction
ComfoNet
no connection between CM
and VM-PCB
error code received from VM
Modbus
Modbus connection error
operating
failed to achieve flow set
system
point within 10 minutes
difference between supply
and extraction air flows is
more than 2.5% for a basic
system and more than 5% for
a connect system
update
update not successful
self-test
failed to run self-test
everything
general undefined and
non-critical errors (e.g. too
high current)
10001124369-0123-zw-zw-A4 ComfoVar Aero Installer_Service Zehnder-General_BOOK_2.indb 61
10001124369-0123-zw-zw-A4 ComfoVar Aero Installer_Service Zehnder-General_BOOK_2.indb 61
location
visualisation
web server and
web server: brief description of
LED
the error and of the possible
cause
LED: ComfoNet LED flashes
fast
Web server and
web server: display the
LED
received error code
LED: the error LED is on
(critical error)
web server and
web server: brief error
LED
description
LED: Modbus LED flashes fast
(e.g. internal fault,
communication fault,
configuration fault)
web server and
web server: brief description of
LED
error
LED: error LED is on
(critical error)
web server and
web server: brief description of
LED
the error and of the possible
cause (e.g. open windows
and/or doors)
LED: the error LED is on
(non-critical error)
LED
all LEDs on the CM-PCB are
flashing
web server
brief description of the fault
and its possible cause (e.g. no
VMs, system not yet
commissioned)
(critical error)
web server and
Web server: provide as much
LED
information as possible
LED: the error LED is on
(non-critical error)
action
N/A
N/A
N/A
N/A
N/A
N/A
restart the self-test until it is
successful
N/A
EN - 61