Version - Fronius Symo 10.0-3 208-240 Instructions De Service

Masquer les pouces Voir aussi pour Symo 10.0-3 208-240:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

General:
Country-specific setting Setup – set country setup
MPP Tracker:
Grid monitoring:
Grid voltage limits:
Grid frequency limits:
Q-Mode:
AC power limit:
AC voltage derating:
Fault Ride Through:

Version

Display of version number and serial number of the PC boards installed in the inverter (e.g.,
for service purposes)
42
Device type
Fam.
Serial number
Version – country setup version
Group – inverter software update group
Tracker 1
Tracker 2 (for Fronius Symo only, except Fronius Symo 15.0-3
208)
GMTi – startup time of the inverter in s
GMTr – restart time in s after a grid error
ULL – grid voltage average value over 10 minutes in V.
LLTrip – detection time for long-term voltage monitoring
UILmax – upper inner grid voltage value in V
UILmin – lower inner grid voltage value in V
FILmax – upper inner grid frequency value in Hz
FILmin – lower inner grid frequency value in Hz
Currently set power factor (cos phi)
(e.g., constant cos(phi)/constant Q/Q(U) characteristic/etc.)
Max. P AC – manual power reduction
Status – ON/OFF voltage-dependent power reduction
GVDPRe – threshold from which the voltage-dependent power
reduction starts
GVDPRv – reduction gradient used to reduce the power, e.g.,
10% per volt higher than the GVDPRe threshold.
Message – activates the sending of an info message via Solar
Net
Status – default setting: OFF
If the function is activated, the inverter does not switch off im-
mediately when a short-term interruption to the AC voltage oc-
curs (outside of the limits set by the grid supplier); instead it
continues to supply power for a defined time.
DB min – default setting: 90%
"Dead Band Minimum" setting (%)
DB max – default setting: 120%
"Dead Band Maximum" setting (%)
k-Fac. default setting: 0

Publicité

Table des Matières
loading

Table des Matières