The inverter is delivered with metal bolts as standard.
Criteria for the
The following criteria must be met for each solar module string when using fuse protection:
Proper Selection
-
of String Fuses
-
-
-
I
N
I
SC
V
14
NOTE! To prevent a risk of fire, faulty fuses must only be replaced by new equiv-
alent fuses.
Option DC OVP
DC+ 2.1
DC+ 1.3
DC+ 1.2
Do not remove cover!
Do not remove cover!
DC+ 1.1
I
> 1.8 x I
N
SC
I
< 2.4 x I
N
SC
U
>/= max. input voltage of inverter being used
N
Fuse dimensions: Diameter 10 x 38 mm
Nominal current of the fuse
Short circuit current for standard test conditions (STC) according to solar module
data sheet
Nominal voltage of the fuse
N
NOTE! The nominal current value of the fuse must not exceed the maximum fuse
protection value specified in the solar module manufacturer's data sheet. If a max-
imum fuse protection value is not specified, please request it from the solar mod-
ule manufacturer.
DC+ 2.3
DC- 1.2
DC+ 2.2
DC- 1.1
Each Terminal: I
Each Terminal: I
= 15 A
= 15 A
max