Code
Description
515
No internal communication
with filter
516
Communication with memory
unit not possible
Power derating due to exces-
517
sive temperature
518
Internal DSP malfunction
519
Communication with memory
unit not possible
520
No feed-in within the last
24 hours from MPPT1
522
DC low String 1
523
DC low String 2
558,
Function incompatibility (one
559
or more PC boards in the in-
verter are not compatible with
each other, e.g., after PC
board replacement)
Power derating due to over-fre-
560
quency
564
Function incompatibility (one
or more PC boards in the in-
verter are not compatible with
each other, e.g., after PC
board replacement)
566
Arc Detector switched off
(e.g., in the event of external
arc monitoring)
572
Power limitation due to power
module
573
Undertemperature warning
581
Setup "Special Purpose Utility-
Interactive" (SPUI) is activated
*) If status code persists: Contact a Fronius-trained service technician
54
Behavior
Warning message on
the display
Warning message of
memory unit
A warning message is
shown on the display
when a power derating
occurs
Warning message on
the display
Warning message of
memory unit
Warning message is
shown on the display
Warning message on
the display
Warning message on
the display
Displayed when grid fre-
quency is too high; the
power is reduced.
Warning message on
the display
This status code is dis-
played every day until
the Arc Detector is reac-
tivated.
Power is limited by the
power module
Warning message on
the display
The inverter is no longer
compatible with the
standards IEEE1547
and IEEE1574.1 be-
cause the islanding
function is deactivated,
frequency-dependent
power reduction is acti-
vated, and the frequen-
cy and voltage limits are
being changed
Remedy
*)
*)
Purge cooling air openings and cool-
ing elements if necessary;
Error is corrected automatically; **)
*)
*)
Acknowledge status code;
Check whether all conditions for
problem-free grid power feed opera-
tion are met (e.g., whether solar mod-
ules are covered with snow); *)
*)
Update inverter firmware; *)
As soon as the grid frequency returns
to the permissible range and the in-
verter is back to normal operation, the
error is automatically corrected; **)
Update inverter firmware; *)
No error!
Confirm the status code by pressing
the "Enter" key
*)
*)
No error!
Confirm the status code by pressing
the "Enter" key