The air fan convention
never stops
In the automatic
position the Boiler
always runs at full
power
The Boiler starts up
"alone"
The power does not
change even if you
manually adjust
Anomalies related to the plumbing circuit
PROBLEM
No increase in
temperature with Boiler
in operation
Condensation
in boiler
Radiators cold in winter
but the Boiler boils
Hot water in not
provided
50
1. Temperature sensor temperature
control defective
or broken
2. Fan failure
1. Room thermostat set to
maximum
2. Temperature sensor defective
3. Control panel defective or broken
1. Incorrect programming of the
cronothermostat
1. The board is set to automatic
correction of power in proportion to
the temperature
POSSIBLE CAUSE
1. Incorrect combustion
adjustment
2. Boiler/system dirty
3. Insufficient Boiler power
1. Incorrect setting maximum
water temperature in the boiler
2. Insufficient fuel consumtion
1. Circulator does not run because
blocked
2. Radiators have air in them
1. Circulator pump blocked
1. Check operation of the sensor and replace if
necessary
2. Check operation of the motor and replace if
necessary
1. Reset the thermostat temperature
2. Check the operation of the sensor and replace if
necessary
3. Check the panel and replace if necessary
1. Check the settings of the cronothermostat
1. Contact your Authorized Assistance Center
REMEDY
1. Check parameters
2. Check and clear the boiler
3. Check that the Boiler is properly sized for the
requirements of the system
1. Set the Boiler to a higher temperature. The
maximum water temperature in the boiler is 65 ° C
and can not be set below 40 ° C or above 80 ° C. It is
advisable to never adjust the temperature below 60 ° C
to avoid condensation in the boiler.
Adjust the power of the pump at a higher
temperature to 60° C.
2. Checking the boiler setting (technical
parameters setting) in order to avoid excessive
fuel consumption, guarantee the expected
heating capacity and safeguard the integrity of
the product
3. Check the correct operation of the anti-
condensation valve
1. Free up the circulator by removing the plug
and turning the shaft with a screwdriver. Check
the electrical connections of the same, replace if
necessary
2. Vent the radiators
1. Free the circulator pump