Lenze 8200 Motec Instructions De Montage page 119

Masquer les pouces Voir aussi pour 8200 Motec:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

All manuals and user guides at all-guides.com
Display
Error
1)
Keypad PC
66
CAN Time-Out
c c c c e e e e 5 5 5 5
a
67
Function module
c c c c e e e e 6 6 6 6
system bus (CAN)
a
on FIF has set
"Warning" or
"BUS-OFF"
(only generated if
C0128 = 1)
91
External fault
E E E E E E E E r r r r
(TRIP-SET)
a
105
Internal fault
H H H H 0 0 0 0 5 5 5 5
a
140
Faulty parameter
i i i i d d d d 1 1 1 1
identification
a
32
Fault in motor
L L L L P P P P 1 1 1 1
phase
a
(only generated if
C0597 = 1)
182
Fault in motor
L L L L P P P P 1 1 1 1
phase
(only generated if
C0597 = 2)
1030 DC-bus
030
C bus
L L L L U U U U
L L L L U U U U
undervoltage
d
c
L
Cause
For remote parameter setting via
system bus (C0370):
Slave does not answer.
Communication monitoring time
exceeded.
For operation with module in
FIF:
Internal fault
CAN controller sets "Warning" or
"BUS OFF"
A digital input assigned to the
TRIP-Set function has been
activated.
Motor not connected
Failure of one/several motor
l
phase(s)
Motor current too low
l
Mains voltage too low
lt
DC-bus voltage too low
400 V controller connected to
240 V mains
EDK82MV222 DE/EN/FR 3.0
Troubleshooting
Error messages
Remedy
Check system bus wiring
l
Check system bus configuration
l
Contact Lenze
Check whether bus terminator
l
available
Check screen contact of the
l
cables
Check PE connection
l
Check bus load, if necessary,
l
reduce the baud rate
Check external encoder
Contact Lenze
Connect motor
Check motor cables,
l
Check V
boost
l
min
Connect motor to corresponding
l
power or adapt the motor under
power or adapt the motor under
C0599.
Check mains voltage
Check supply module
Connect controller to the appropriate
mains voltage
?
55