Commissioning
7
Vector control
Switch-on sequence
13.
Adapt the voltage/current range to
the analog setpoint (C0034)
Lenze setting: -0-, (0 ... 5 V/0 ... 10
V/0 ... 20 mA)
14.
Enter the motor data
A. Rated motor speed (C0087)
Lenze setting: 1390 rpm
B. Rated motor current (C0088)
Lenze setting: Depending on the
controller
C. Rated motor frequency (C0089)
Lenze setting: 50 Hz
D. Rated motor voltage (C0090)
Lenze setting: Depending on the
controller
E. Motor cos ϕ (C0091)
Lenze setting: Depending on the
controller
15.
Motor parameter identification
(C0148)
A. Ensure that the controller is inhibited
(terminal X3/28 = LOW)
B. Set C0148 = 1
v
in addition
C. Enable the controller
(terminal X3/28 = HIGH)
D. If the segment becomes active after
c
approx. 30 s,
must be activated.
(terminal X3/28 = LOW)
16.
If necessary, adjust more
parameters
After parameter setting:
17.
Setpoint selection
38
z
w x
y
z
w x
y
The motor makes a high-pitched
tone. The motor does not rotate!
Calculated and stored:
controller inhibit
V/f rated frequency (C0015)
l
Slip compensation (C0021)
l
Motor stator inductance (C0092)
l
Measured and stored:
Motor stator resistance (C0084)
l
= Total resistance of motor cable
and motor
E. g. JOG frequencies (C0037,
C0038, C0039), deceleration time
for quick stop (QSP) (C0105) or
motor temperature monitoring
(C0119)
E.g. via potentiometer at terminals
7, 8, 9
EDK82MV222 DE/EN/FR 3.0
Note
Set the DIP switch on the
d
c
b
e
a
j g f k i h PS
standard-I/O to the same
m n o
p
q
r
range (see Mounting
Hi
Hz
Lo
Instructions for the
standard-I/O)
See motor nameplate
Enter the value for the
motor connection type
(star/delta) selected!
Enter the value for the
motor connection type
(star/delta) selected!
d
c
b
e
a
j g f k i h PS
m n o
p
q
r
Hi
Hz
Lo
Identification starts, the
segment
Identification is completed.
c
is off.
L