Code
No.
Name
C0111
Configuration
v
analog output
X3/62 (AOUT1-IN)
C0117
Fixed
v
configuration of
digital output A1
(DIGOUT1)
C0119
Configuration PTC
v
v
input / earth fault
input / earth fault
detection
2
C0120
I
t switch-off
C0140*
Added frequency
setpoint
(NSET1-NADD)
C0142
Start condition
v
v
C0143*
Selection of
v
v
flying-restart
flying-restart
L
Possible settings
Lenze
Choice
-0-
-0-
Output frequency with slip
(MCTRL1-NOUT+SLIP)
-0-
-0-
Ready for operation (DCTRL1-RDY)
-0-
-0-
PTC input not
active
-1-
PTC input active,
TRIP set
-2-
PTC input active,
Warning set
-3-
PTC input not
active
-4-
PTC input active,
TRIP set
-5-
PTC input active,
Warning set
0
0
= not active
-650.00
-1-
-0-
Automatic start inhibited
Flying restart not active
-1-
Automatic start, if X3/28 = HIGH
Flying restart not active
-2-
Automatic start inhibited
Flying-restart circuit active
-3-
Automatic start, if X3/28 = HIGH
Flying-restart circuit active
-0-
Max. output frequency (C0011) ... 0
-0-
Hz
-1-
Last output frequency ... 0 Hz
-2-
Frequency setpoint addition
(NSET1-NOUT)
-3-
Act. process controller value
(C0412/5) addition (PCTRL1-ACT)
EDK82MV222 DE/EN/FR 3.0
Commissioning
Code table (excerpt)
Earth fault
detection active
detection active
Earth fault
detection
detection
{%}
200 Reference: Apparent
{Hz}
650.00 Application I/O supports
7
IMPORTANT
See the Operating
Instructions for further
settings
6 V/12 mA
C0011
See the Operating
Instructions for further
settings
Deactivate the earth fault
detection if it has been
detection if it has been
activated unintentionally
motor current (C0054)
650 Hz as of version
E82AF ... XXVB21
Selection via function
l
j
of the keypad or
the parameter
channel
Non-volatile saving of
l
the value (i.e. active
after mains
switching); value is
added to the main
setpoint
Start after LOW-HIGH
level change at X3/28
Start after LOW-HIGH
level change at X3/28
Motor speed selected for
the indicated range
the indicated range
The corresponding value
is input after controller
is input after controller