salmson SIE Serie Installation Et Mise En Service page 112

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
English
No.
Designation
5.3.1.0
In1 (sensor value
range)
5.3.2.0
In1 (value range)
5.4.0.0
In2
5.4.1.0
In2 active/inactive
5.4.2.0
In2 (value range)
5.5.0.0
PID parameters
5.5.1.0
P parameter
5.5.2.0
I parameter
5.5.3.0
D parameter
5.6.0.0
Fault
5.6.1.0
HV/AC
5.6.2.0
Emergency opera-
tion speed
5.6.3.0
Auto reset time
5.7.0.0
Other settings 1
5.7.1.0
Display orientation
5.7.2.0
Pressure value cor-
rection
104
Type
Symbol Values/explanations
Display of sensor value range 1
±
Setting of the value range
Possible values: 0...10 V/2...10 V/
0...20 mA/4...20 mA
Setting for external setpoint
input 2
±
ON
External setpoint input 2 active
OFF
External setpoint input 2 inac-
tive
±
Setting of the value range
Possible values: 0...10 V/
2...10 V/0...20 mA/4...20 mA
Settings for PID control
±
Setting of the proportional term
of the control
±
Setting of the integral term of
the control
±
Setting of the derivative term of
the control
Settings for behaviour in case of
error
±
HV "heating" mode
AC "cooling/air-conditioning"
mode
Display of emergency operation
speed
±
Time until automatic acknowl-
edgement of an error
±
Display orientation
Display orientation
±
When pressure value correction
is enabled, the differential pres-
sure deviation measured by the
differential pressure sensor that
is factory-fitted on the pump
flange is taken into account and
corrected.
Pressure value correction off
Pressure value correction on
Display conditions
Not displayed with PID
control
Not displayed when In2 =
inactive
Only displayed when PID
control is active (incl. all
sub-menus)
Only displayed in
p-c mode.
Δ
Is not displayed for all pump
variants.
Salmson 05/2015

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Die seriePbe serie

Table des Matières