4.4.16
Information concernant UL
REMARQUE
Les chapitres suivants sont toujours en anglais indépendamment de la langue de la
présente documentation et ce, en raison des prescriptions UL.
Thermal motor protection
Thermal motor overload protection shall be provided by one of the following means:
Parameter
The following additional parameter was added to MOVITRAC
implement internal thermal motor protection according to NEC:
Functional principle
The motor current is accumulated in an internal memory over the course of time. The
inverter goes to fault state as soon as the thermal limit is exceeded (I.t-trP).
Once the output current of the inverter is less than the set rated motor current, the in-
ternal memory is decremented depending on the output current.
NEC compliant installation of a motor temperature sensor, see also section "Motor
temperature protection (TF/TH)" in the chapter "Electrical Installation" of the opera-
ting instructions.
Using internal thermal motor overload protection according to NEC (National Elec-
trical Code, US). Thermal motor overload protection can be activated via parame-
ter P4-17.
Implementing external measures to ensure thermal motor overload protection
according to NEC (National Electrical Code).
P4-17 Thermal motor protection according to NEC
– 0: disabled
– 1: enabled
When P4-17 is disabled, thermal memory retention is reset upon shutdown or po-
wer loss.
When P4-17 is enabled, thermal memory retention is maintained upon shutdown
or power loss.
Installation
Installation électrique
®
LTP-B/LTX inverters to
Notice d'exploitation – MOVITRAC
4
37
®
 LTP B