ProGramminG
Pressure transmitter 8311
.1 General recommendations
Keep in mind that the process may be influenced by all the parameter
settings you make. Fill-in the table on pages 35 -36 with your settings of
the transmitter.
.2 functionalities
The device has three operating modes:
normal mode (see p.21)
Display of the measured pressure, the value of the output current and the
values of the min. and max. process pressures.
From the Normal mode, you can access the Calibration and Test modes.
the access to the calibration and the test modes can be protec-
ted by a 4-digit code, disabled by default; it can be programmed
in the calibration mode.