Test Mode - Burkert 8311 Manuel D'installation

Masquer les pouces Voir aussi pour 8311:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles


ProGramminG

. test mode

to test the transmitter beha-
viour after entering a pressure
value and PRESSING THE
ENTER KEY.
Zero -> disP
to display the difference
in % between the zero point
calibrated ex works and the
last calibrated zero point.
Zero -> cal
to adjust the zero point of
the transmitter, at nil pres-
sure, with respect to the zero
point calibrated ex works.
Kfac -> disP
to display the difference
in % between the K factor
calibrated ex works and the
last calibrated K factor.
Kfac -> cal
to adjust the K factor of
the transmitter, at a standard
pressure, with respect to the
K factor calibrated ex works.
3
1.500
TEST
ENTER
ENTER
SIM UNIT
SIM
0......9
*
TEST
ENTER
DISP
ENTER
ZERO
0......9
ENTER
CAL
1)
0......9
TEST
ENTER
DISP
ENTER
KFAC
0......9
ENTER
CAL
1)
The transmitter operates with the previous calculated value.
1)
The transmitter memorizes the pressure applied in the process.
2)
TEST
3.95
ENTER
ma
OFFS ma
Alternating display of the function and
the selected unit
SIM UNIT
Zero point must be adjusted
before K factor!
15.20
ENTER
% ZERO
% ZERO < 20% ?
0.205
ENTER
TEACH ZERO
% ZERO > -20% ?
no
Enter the value of the standard pressure (within the
measuring range) applied to the process.
01.00
ENTER
% KFAC
10.00
9.985
ENTER
UNIT
TEACH KFAC
2)
0......9
*
20.50
ENTER
ENTER
SPAN ma
0......9
Pressure transmitter 8311
yes
15.20
&
% ZERO
yes
% KFAC < 20% ?
01.00
ENTER
&
% KFAC > -20% ?
% KFAC
no
ENTER
ENTER

Publicité