Chapter 5
Fig. 4: Circuit diagram for the
UE4215 and pin assignments
for the M12 socket for the
connection of the sender
power supply
Tab. 4: Pin assignment
socket AUX PWR
Note
Fig. 5: Wiring example:
Connection of light curtains
or light grids to the UE4215;
Functional earthing via
AS/interface slave and base
96
© SICK AG • Industrial Safety Systems • Germany • All rights reserved
Electrical installation
5.1.2

M12 socket AUX PWR (sensor voltage supply)

If power is to be supplied to the sender for the sensor pair via the safe bus node
UE4215, connect the sender to the M12 AUX PWR socket.
Pin 2
Pin 1
Pin 5
Pin
Wire colour
1
Brown
2
White
3
Blue
4
Black
5
Grey
5.2

Wiring examples

Observe the note concerning the functional earth in chapter 4.2, "Mounting the device".
Function
AUX L+ (24 V)
Not assigned
AUX L–
AUX L+ (24 V)
Functional earth (FE)
Receiver, e.g. SICK C40E, C20E, M20E