Burkert 8012 Manuel D'utilisation page 34

Masquer les pouces Voir aussi pour 8012:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

brown
white
green
YE GY BN WH GN
grey
Fig. 14 : NPN wiring (default) of the pulse output of a version with
cable gland
brown
white
green
YE GY BN WH GN
grey
Fig. 15 : PNP wiring of the pulse output of a version with cable
gland
34
12-36 VDC
Power supply
+ -
(*)
Load
12-36 VDC
Power supply
+ -
(*)
Load
English
Type 8012
Installationandwiring
4-20mA input
at external
device
+ -
YE GY BN WH GN
Fig. 16 : Wiring the current output in sinking mode (by default) on a
version with cable gland
(*) Functional earth; If a direct earth connection is not possible, fit a 100 nF /
50 V capacitor between the negative power supply terminal and the earth.
4-20mA input
at external
device
+ -
YE GY BN WH GN
Fig. 17 : Wiring the current output in sourcing mode on a version
with cable gland
(*) Functional earth; If a direct earth connection is not possible, fit a 100 nF /
50 V capacitor between the negative power supply terminal and the earth.
12-36 VDC
Power
supply
+ -
(*)
12-36 VDC
Power
supply
+ -
(*)
green