Technical Data - Burkert 0911 Instructions De Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3

TECHNICAL DATA

• Housing
• Dimensions
• Assembly
• Protection class
• Connections
• Pipe cross-section
• Auxiliary energy
• Power consumption
• Display
• Inputs
• Relay outputs
• Data memory
• Ambient temperature
• Storage temperature
• Air humidity
• Measurement range
• Resolution
• Accuracy at +25 °C
14 - 0911
ABS, self-extinguishing
Front 74 x 32 mm, Depth 60 mm
Panel-mounting unit for 29 x 71 mm cutout
IP65 from front, only with front seal RG-C
IP20
Screw terminals
≤2.5 mm
2
depending on model
12...24 V AC/DC; ±10%
230 V AC; ±10%; 50/60 Hz
optional 110 V AC; ±10%; 50/60 Hz
max. 3 VA
3½ digits, red LED, height 12 mm
configurable NTC / PTC or
NTC / PTC / Pt100 / Thermoelement J, K, S
or 4... 20 mA / 0...1 V / 0...10 V
2 x NO 8(3) A, 250 V AC + 1 x NC
EEPROM
0...+60°C / +32...+140°F
-30...+85°C / -22...+185°F
20...85% (non-condensing)
according to sensor
0.1°C or 1°F
better than 0.5% of the limit value of the
measurement range