Alarms
Hysteresis for the
ALH
Limit value alarms
ALL and ALU
dAO
Alarm delay at
with Mains ON
Status of Control Relay 1
So1
with sensor fault
So2
Status of Control Relay 2
with sensor fault
tbA
Status of the control relay
after acknowledgement by
of an alarm situation
AS
Configuration of the alarm
relay at an alarm
Measured value display
Lower analog
LCI
Display value
(-1999...1999)
UCI
Upper analog
display value
(-1999...1999)
OPb
calibration of the sensor
Resolution
rES
UdM
Units
PbC
Type of sensor
Temperature sensor U):
current/voltage input
(AU)
P3F
Third terminal of a
Pt100 sensor
Automatic alarm acknowledgement:
With high alarm undershot by
ALU - ALH and with low alarm with
under shooting of ALL + ALH
0...23.5 hours; suppression of
Alarms after commissioning.
oFF = opened
on = closed
oFF = opened
on = closed
oFF = Relay deactivated
on = Relay activated
cL = Terminal 5-6 closed
oP = Terminal 5-6 closed
scaling of the lower display value at
Current input 4 mA or at
Voltage input 0 V (only for the
inputs 0-20 mA, 0-1V, 0-10 V)
Scaling of the upper display value at
current input 20 mA or with voltage
input 1 V and 10 V (only for the
inpits 0-20 mA, 0-1V, 0-10 V)
regardless of the measurement range
in = only whole numbers
dE = also tenths
ce = hundreths
Display of the units directly in the
illuminated display. Regardless of which
controller type is being used:
see General description
Type of inout
J = Thermoelement „J"; Pt = Pt100;
C = Thermoelement „K"; Ptc = PTC;
S = Thermoelement „S"; ntc = NTC
cur = 4...20 mA; 0-1 = 0...1 V;
10 = 0...10 V
(if present)
no = Pt100 2-wire wired
yES = Pt100 3-wire wired
0911 - 11