Parameters - Burkert 0911 Instructions De Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2.5

Parameters

Control
Hysteresis 1
Hy1
Hy2
Hysteresis 2
Lowest set-value setting
LS1
Lowest set-value setting
LS2
US1
Highest set-value setting
Highest set-value setting
US2
S1C
Control function 1
S2C
Control function 2
Minimum switch-off period
AC
ouc
Dependency of the
set-values
on
Minimum switch-on period
ono
Minimum delay
Alarms
Configuration
ALC
Temperature alarm
ALL
Low temperature alarm
ALU
Over-temperature alarm
ALd
Alarm delay
at temperature
Overshoot/Undershoot
10 - 0911
Switch hysteresis of Set-value 1 with
positive or negative values. The default
range is dependent on the input type.
The parameter may not be entered as
zero. The control function is predefined
with S1C.
Switch hysteresis of Set-value 2 with
positive or negative values(as Hy1).
The control function is predefined with
S2C.
Set-value limits 1 for operator
Set-value limits 2 for operator
Set-value limits 1 for operator
Set-value limits 2 for operator
in = inverted (Heating, humidifying)
dir = direct (cooling, dehumidifying)
in = inverted (heating, humidifying)
dir = direct (cooling, dehumidifying)
0 ... 250 sec relay switch-off period
diP = dependent
ind = independent
0...250 sec relay switch-on period
0...120 min; minimum delay between two
activations of the control relay.
rE = relative to the set-value (in Kelvin)
Ab = absolute values (in °C)
If SET - ALL is undershot, a low
temperature alarm will be triggered after
the delay time ALd.
If SET + ALU exceeded, a high
temperature alarm will be triggered after
delay time ALd.
0...999 min; Minimum time in which the
conditions for an alarm situation
must be present.

Publicité

Table des Matières
loading

Table des Matières