2.5

Controlling the loads

CONTROLLER OUTPUT
The control is dependent on the measured temperature (= sensor
temperature). Program the control direction (heating or cooling) with the
parameter S1C.
S1C = dir
S1C = in
COOLING
temperature
SET+HY
SET
compressor
ON
Parameter S1C = dir; The value HY has been preset to 2 K in the factory.
If the temperature exceeds the value SET + HY, the compressor will be
switched on and will be switched off again when the temperature is below SET.
HEATING
temperature
SET
SET-HY
heat
ON
Parameter S1C = in; The value HY has been preset to 2 K in the factory.
If the temperature falls below the value SET-HY, the controller output will be
switched on and will be switched off again when SET is exceeded.
Cooling
Heating
SET = Set-value
Hy =
Switch hysterisis
t
t
t
t
0911 - 11