Alarms
Hysteresis for the
ALH
Limit value alarms
ALL and ALU
dAO
Alarm delay at
with Mains ON
Status of the control relay
S01
with sensor fault
tbA
Status of the control relay
after acknowledgement (by
(any button) in an
alarm situation
Configuration of the alarm
AS
relay at an alarm
Measured value display
LCI
Lower analog
Display value
(-1999...1999)
Upper analog
UCI
Display value
(-1999...1999)
OPb
calibration of the sensor
rES
Resolution
Units
UdM
PbC
Type of sensor
Temperature sensor U):
Current / voltage input
(AU)
P3F
Third terminal of a
Pt100 sensor
Automatic alarm acknowledgement:
With high alarm undershot by
ALU - ALH and with low alarm with
under shooting of ALL + ALH
(0.1 K...upper measurement range)
0...23.5 hours; suppression of
Alarms after commissioning.
oFF = opened
on = closed
oFF = Relay deactivated
on = Relay activated
cL = Terminal 4-5 closed
oP = Terminal 4-6 closed
Lower display value for current input
4 mA or with voltage input 1 V
or 10 V (only for inputs 4-20
mA, 0-1V, 0-10 V)
Upper display value for current input
20 mA or for voltage input 1 V or 10 V
(only for the 4-20 mA, 0-1V, 0-10 V
inputs)
regardless of the measurement range
in = only whole numbers
dE = also tenths
ce = hundreths
Display of the units directly in the
illuminated display. Regardless of which
controller type is being used:
see General description
Type of inout
J = Thermoelement „J"; Pt = Pt100;
C = Thermoelement „K"; Ptc = PTC;
S = Thermoelement „S"; ntc = NTC
cur = 4...20 mA; 0-1 = 0...1 V;
10 = 0...10 V
(if present)
no = Pt100 2-wire wired
yES = Pt100 3-wire wired
0911 - 9