MEASUREMENT LIMITS FOR THE SENSOR TYPES
Sensor
NTC
PTC
Pt100
TcK
TcJ
TcS
2.4

Parameters

Control
Hysteresis 1
Hy1
LS1
Lowest set-value setting
Highest set-value setting
US1
S1C
control effect
AC
Minimum switch duration
on
Minimum switch-on period
Minimum delay
ono
Alarms
ALC
Configuration
Temperature alarm
ALL
Low temperature alarm
ALU
Over-temperature alarm
ALd
Alarm delay
at temperature
Overshoot/Undershoot
8 - 0911
Lower limit
-40°C
-50°C
-200°C
0°C
0°C
0°C
Switch hysteresis of Set-value 1 with
positive or negative values. The default
range is dependent on the input type.
The parameter may not be entered as
zero.
Set-value limits for operator
Set-value limits for operator
in = inverse (heating, humidification)
dir = direct (cooling, dehumidification)
0...250 sec relay switch-off duration
0...250 sec relay switch-on period
0...120 min; minimum delay between two
activations of the control relay.
rE = relative to the set-value (in Kelvin)
Ab = absolute values (in °C)
If SET - ALL is undershot,
a low temperature alarm will be triggered
after the delay time ALd.
If SET + ALU exceeded, a high
temperature alarm will be triggered after
delay time ALd.
0...999 min; Minimum time in which the
conditions for an alarm situation
must be present.
Upper limit
110°C
150°C
600°C
1300°C
600°C
1400°C