3.0 minimum venting requirements

minimum venting requirements
EN
WARNING
!
Risk of fi re. Maintain specifi ed air space clearances to vent pipe and appliance.
The vent system must be supported every 3'(0.9m) for both vertical and horizontal runs. Use support ring
assembly W010-0067 or equivalent non-combustible strapping to maintain the minimum clearance to
combustibles for both vertical and horizontal runs. Spacers are attached to the inner pipe at predetermined
intervals to maintain an even air gap to the outer pipe. This gap is required for safe operation. A spacer is
required at the start, middle, and end of each elbow to ensure this gap is maintained. These spaces must
not be removed.
This appliance uses a 5" (127mm) exhaust / 8" (203.2mm) air intake vent pipe system. Refer to the
This appliance uses a 5" (127mm) exhaust / 8" (203.2mm) air intake vent pipe system. Refer to the
section applicable to your installation.
section applicable to your installation.
For safe and proper operation of the appliance follow the venting instructions exactly. Deviation from the
For safe and proper operation of the appliance follow the venting instructions exactly. Deviation from the
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent
minimum vertical vent length can create difficulty in burner start-up and/or carboning. Under extreme vent
confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Although not a requirement,
configurations, allow several minutes (5-15) for the flame to stabilize after ignition. Although not a requirement,
it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl spaces) be
it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl spaces) be
insulated with the insulation wrapped in a protective sleeve to minimize condensation. Provide a means for
insulated with the insulation wrapped in a protective sleeve to minimize condensation.
visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent pipe
Provide a means for visually checking the vent connection to the appliance after the appliance is installed.
shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
Use a firestop, vent pipe shield or attic insulation shield when penetrating interior walls, floor or ceiling.
The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint
suitable for 400°F (200°C). Application and performance of paint is the consumer's responsibility. Spot testing is
The vent terminal may be painted with high temperature paint to match exterior colours. Use an outdoor paint
recommended.
suitable for 400°F (200°C). Application and performance of paint is the consumer's responsibility. Spot testing is
note:
recommended. Appliance should be off.
If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the
note:
initial installation.
If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing
initial installation.
alternate constructions, such as a chimney as part of the vent system, is not permitted.
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing
alternate constructions, such as a chimney as part of the vent system, is not permitted.
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting
components. Minimum and maximum vent lengths, for both horizontal and vertical installations, clearances from
vent pipes to combustibles and air terminal locations as set out in this manual apply to all vent systems and
All vent measurements start at the base of the air collar of the appliance.
must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab,
follow the installation procedure provided with the venting components. A starter adaptor must be used with the
following vent systems and may be purchased from the corresponding supplier:
important:
Vent
For ease of installation, the front frame can be removed. The front frame must be
Manufacturer
reinstalled prior to installing the nailing tabs.
Duravent
Amerivent
Horizontal vent sections: A minimum clearance of 3" (76mm) on the top outside of the enclosure and 2"
(51mm) on the sides and bottom outside of the enclosure all around the vent pipe on all horizontal runs to com-
Direct Temp
bustibles is required. Horizontal vent sections within enclosures require a minimum clearance of 6" (152mm) at
SuperSeal
the top of the vent pipe.
Vertical vent sections: A minimum of 1" (25mm) all around the vent pipe on all vertical runs to combustibles is
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using
required except for clearances in appliances enclosures. Vertical vent sections within enclosures require a mini-
a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake
mum clearance of 1" (25mm) around the vent pipe.
vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance
fl ue collar which must be sealed using the black high temperature sealant Mill Pac.
This template must be used in conjunction with templates 7.2.1 or 7.2.2, depending on termina-
tion shape (i.e. round, or round and square). See appropriate templates folder.
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to
a minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year
to verify that it is unobstructed and undamaged.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components
must not be combined.
14
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal
W415-1710 / B / 08.17.18
run is 20 feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of
vent connections is two horizontally or three vertically (excluding the appliance and the air terminal connections)
Starter Adapter Part
Number
W175-0170
5DSC-N2
5DT-AAN
5DNA
Supplier
Website
Wolf Steel
www.duravent.com
American Metal
www.americanmetalproducts.com
Selkirk
www.selkirkcorp.com
Metal-Fab
www.mtlfab.com