Minimum Venting Requirements - Napoleon Ascent Multiface Serie Manuel D'installation Et D'opération

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.0 minimum venting requirements

minimum venting requirements
EN
WARNING
!
WARNING
Risk of fi re. Maintain specifi ed air space clearances to vent pipe and appliance.
!
The vent system must be supported every 3'(0.9m) for both vertical and horizontal runs. Use support ring
assembly W010-0067 or equivalent non-combustible strapping to maintain the minimum clearance to
Risk of fi re. Maintain specifi ed air space clearances to vent pipe and appliance.
combustibles for both vertical and horizontal runs. Spacers are attached to the inner pipe at predetermined
The vent system must be supported every 3'(0.9m) for both vertical and horizontal runs. Use support ring
intervals to maintain an even air gap to the outer pipe. This gap is required for safe operation. A spacer is
assembly W010-0067 or equivalent non-combustible strapping to maintain the minimum clearance to
required at the start, middle, and end of each elbow to ensure this gap is maintained. These spaces must
combustibles for both vertical and horizontal runs. Spacers are attached to the inner pipe at predetermined
not be removed.
intervals to maintain an even air gap to the outer pipe. This gap is required for safe operation. A spacer is
required at the start, middle, and end of each elbow to ensure this gap is maintained. These spaces must
This appliance uses a 5" (127mm) exhaust / 8" (203.2mm) air intake vent pipe system. Refer to the
not be removed.
section applicable to your installation.
For safe and proper operation of the appliance follow the venting instructions exactly. Deviation from the
This appliance uses a 5" (127mm) exhaust / 8" (203.2mm) air intake vent pipe system. Refer to the
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent
section applicable to your installation.
confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Although not a requirement,
For safe and proper operation of the appliance follow the venting instructions exactly. Deviation from the
it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl spaces) be
minimum vertical vent length can create diffi culty in burner start-up and/or carboning. Under extreme vent
insulated with the insulation wrapped in a protective sleeve to minimize condensation. Provide a means for
confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition. Although not a requirement,
visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent pipe
it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl spaces) be
shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
insulated with the insulation wrapped in a protective sleeve to minimize condensation. Provide a means for
visually checking the vent connection to the appliance after the appliance is installed. Use a fi restop, vent pipe
The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint
shield or attic insulation shield when penetrating interior walls, fl oor or ceiling.
suitable for 400°F (200°C). Application and performance of paint is the consumer's responsibility. Spot testing is
recommended.
The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint
suitable for 400°F (200°C). Application and performance of paint is the consumer's responsibility. Spot testing is
note:
recommended.
If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the
initial installation.
note:
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing
If for any reason the vent air intake system is disassembled; reinstall per the instructions provided for the
alternate constructions, such as a chimney as part of the vent system, is not permitted.
initial installation.
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing
You may reduce the appliance from 5/8" venting to 4/7" venting for horizontal and vertical rise applications.
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting
alternate constructions, such as a chimney as part of the vent system, is not permitted.
Reducing must be done right off of the appliance and a new firestop spacer (W010-3440) will be required.
components. Minimum and maximum vent lengths, for both horizontal and vertical installations, clearances from
vent pipes to combustibles and air terminal locations as set out in this manual apply to all vent systems and
Use only Wolf Steel, Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent or Metal-Fab venting
must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab,
components. Minimum and maximum vent lengths, for both horizontal and vertical installations, clearances from
follow the installation procedure provided with the venting components. A starter adaptor must be used with the
vent pipes to combustibles and air terminal locations as set out in this manual apply to all vent systems and
following vent systems and may be purchased from the corresponding supplier:
must be adhered to. For Simpson Dura-Vent, Selkirk Direct Temp, American Metal Amerivent and Metal-Fab,
follow the installation procedure provided with the venting components. A starter adaptor must be used with the
Vent
following vent systems and may be purchased from the corresponding supplier:
Manufacturer
Vent
Duravent
Manufacturer
Amerivent
Duravent
Direct Temp
Amerivent
SuperSeal
Direct Temp
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using
SuperSeal
a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake
vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance
For vent systems that provide seals on the inner exhaust fl ue, only the outer air intake joints must be sealed using
fl ue collar which must be sealed using the black high temperature sealant Mill Pac.
a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and outer intake
vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the appliance
This template must be used in conjunction with templates 7.2.1 or 7.2.2, depending on termina-
fl ue collar which must be sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / fl exible components with the
tion shape (i.e. round, or round and square). See appropriate templates folder.
following termination kits: wall terminal kit GD422R-2, or 1/12 to 7/12 pitch roof terminal kit GD410, 8/12 to
This template must be used in conjunction with templates 7.2.1 or 7.2.2, depending on termina-
12/12 roof terminal kit GD411, fl at roof terminal kit GD412 or periscope kit GD401 (for wall penetration below
tion shape (i.e. round, or round and square). See appropriate templates folder.
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to
grade). With fl exible venting, in conjunction with the various terminations, use either the 5 foot (1.5m) vent kit
a minimum.
GD420 or the 10 foot (3.1m) vent kit GD430.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year
For optimum fl ame appearance and appliance performance, keep the vent length and number of elbows to
to verify that it is unobstructed and undamaged.
a minimum.
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year
must not be combined.
to verify that it is unobstructed and undamaged.
10
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal
Rigid and fl exible venting systems must not be combined. Different venting manufacturer components
W415-1285 / H / 08.07.18
run is 20 feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of
must not be combined.
vent connections is two horizontally or three vertically (excluding the appliance and the air terminal connections)
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal
Starter Adapter Part
Number
Starter Adapter Part
W175-0170
Number
5DSC-N2
W175-0170
W175-0053
5DT-AAN
5DSC-N2
4DSC-N2
5DNA
5DT-AAN
4DT-AAN
5DNA
4DNA
Supplier
Website
Wolf Steel
www.duravent.com
Supplier
Website
American Metal
www.americanmetalproducts.com
Wolf Steel
www.duravent.com
Selkirk
www.selkirkcorp.com
American Metal
www.americanmetalproducts.com
Metal-Fab
www.mtlfab.com
Selkirk
www.selkirkcorp.com
Metal-Fab
www.mtlfab.com
7.2.2

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Ascent multiface bhd4pnAscent multiface bhd4stnAscent multiface bhd4pgnAscent multiface bhd4stgnAscent multiface bhd4pfcnAscent multiface bhd4stfcn ... Afficher tout

Table des Matières