3 Classification of the condensing units and of its
components according to the EU directives
The condensing units are intended for incorporation
into machines in accordance with the EU Machinery
Directive 2006/42/EC. The electrical components com-
ply with the EU Low Voltage Directive 2014/35/EU. For
the incorporated pressurised components, the EU
Pressure Equipment Directive 2014/68/EU (PED) may
be applicable, except for the compressors (see below).
The corresponding declarations of conformity and man-
ufacturers' declarations are available. Classification of
the individual components and additional explanations
see table 1, page 5.
Component
Compressor, semi-her-
metic
Discharge gas shut-off
valve
Suction gas shut-off valve
Condenser, air-cooled
Condenser fan
Liquid line, condensate
line
Pipe joints
Discharge gas line
Pipe joints
Suction gas line
Pipe joints
Liquid receiver
Liquid shut-off valve
Ball valve
Oil separator
Check valve
Filter drier
Sight glass
HP limiter/
HP cut-out
LP limiter
Discharge gas temperat-
ure sensor
KB-206-1
PED ①
MD
LVD
Art. 4
X
X
(3.10)
Art. 4 (3)
Art. 4 (3)
Art. 4 (3)
Art. 4 (3)
Art. 4 (3)
I/II
Art. 4 (3)
Art. 4 (3)
II
Art. 4 (3)
Art. 4 (3)
I
Art. 4 (3)
Art. 4 (3)
Art. 4 (3)
IV
IV
Art. 4 (3)
Information
Condensing units are not considered a "func-
tional whole" according to the PED and do
therefore not fall within the scope of Art.1 §
2.1.5 "Assemblies". The directive is therefore
only applied to the individual components. The
same applies to the CE marking. Assessment
by a notified body: Bureau Veritas, Paris –
"Technical Appraisal" for ASERCOM members
PED-TA_ASE_001_01-DEU.
Information
According to Article 4 § 3.10, semi-hermetic and
open drive compressors are excluded from the
application range of the PED. This exception is
confirmed by the evaluation of a notified body.
Please refer to "Explanations about the product
conformity" AC-100 for further explanations.
Please refer to AC-100 for the classification of
pressurised accessories for compressors.
EMC
CE mark-
Comments
ing
X
Accessories, see explanation
AC-100
≤ DN25 / PS 32 bar
≤ DN32 / PS 32 bar
≤ DN25 / PS 32 bar
X
X
X ②
≤ DN25 / PS 32 bar, detachable
joint ②
≤ DN32 permanent joint ②
≤ DN25 / PS 32 bar
according to DN
≤ DN25 / PS 19 bar
Detachable joint ≤ DN25
< 6.25 .. 31.25 dm
≤ DN25 / PS 32 bar
X
< 6.25 dm
≤ DN32 / PS 32 bar
< 1.56 dm
< 1 dm
With safety function
With safety function
≤ DN25
3
/ PS 32 bar
3
/ PS 32 bar
3
/ PS 32 bar
3
/ PS 32 bar
5