Menu item
F4⇒SCr⇒dS3
Modbus: 9016
(read only)
F4⇒SCr⇒HS3
Modbus: 9010
(read only)
Display of the registered alarms (20 memory locations):
Menu item
F4⇒HiSt⇒HYSP
Modbus: 9023
(read and write)
F4⇒HiSt⇒HYSC
Modbus: 9024
(read only)
F4⇒HiSt⇒HYSd
Modbus: 9024
(read only)
F4⇒HiSt⇒HYSt
Modbus: 9026
(read only)
F4⇒HiSt⇒HiSF
Modbus: 9027
(read only)
The ECOLITE controller has an alarm memory for up to
20 error messages, which remain stored together with
a time stamp. The latest error message can be found in
the memory location 0.
Menu item
F4⇒CLOC⇒HOUr
Modbus:
(read and write)
F4⇒CLOC⇒Min
Modbus:
(read and write)
F4⇒CLOC⇒dAY
Modbus:
(read and write)
F4⇒CLOC⇒MOnt
20
Function
Operating hours counter of compressor
Number of days compressor has been operating
Operating hours counter of compressor
Number of hours compressor has been operating
Function
Alarm list memory locations
0 – 19 memory locations
0 = most recent memory location for last message
Alarm list alarm numbers
Alarm list date
Format DD.MM
Alarm list time
Format HH:MM
Alarm list number of stored error messages
Function
Setting of ECOLITE controller time – hour
0 – 24
Setting of ECOLITE controller time – minute
0 – 59
Setting of ECOLITE controller date – day
0 – 31
Setting of ECOLITE controller date – month
Display and setting of date and time of the ECOLITE
controller:
KB-206-1