Display of the status of the digital inputs of the
controller:
Menu item
F4⇒di⇒diL1
Modbus: 8192
(read only)
F4⇒di⇒diL2
Modbus: 8193
(read only)
F4⇒di⇒diL3
Modbus: 8194
(read only)
F4⇒di⇒diL4
Modbus: 8195
(read only)
F4⇒di⇒diL5
Modbus: 8196
(read only)
F4⇒di⇒diL6
Modbus: 8197
(read only)
Display of the operating times:
Menu item
F4⇒SCr⇒dS1
Modbus: 9012
(read only)
F4⇒SCr⇒HS1
Modbus: 9006
(read only)
F4⇒SCr⇒dS2
Modbus: 9014
(read only)
F4⇒SCr⇒HS2
Modbus: 9008
(read only)
KB-206-1
Function
Status of controller digital input DI01
Safety chain of ECOLITE condensing unit
OFF = compressor off or safety chain was triggered
On = compressor is running, safety chain is OK
Status of controller digital input DI02
Reserve
Status of controller digital input DI03
Reserve
Status of controller digital input DI04
Reserve
Status of controller digital input DI05
Configurable special function 1. Input
OFF = there is no external On command active
On = an external On command is active
Status of controller digital input DI06
Configurable special function 2. Input
OFF = there is no external On command active
On = an external On command is active
Function
Operating hours counter of CR II solenoid valve 1
Number of days solenoid valve has been operating
Operating hours counter of CR II solenoid valve 1
Number of hours solenoid valve has been operating
Operating hours counter of CR II solenoid valve 2
Number of days solenoid valve has been operating
Operating hours counter of CR II solenoid valve 2
Number of hours solenoid valve has been operating
19