If room temperature control is set, the solenoid valve of
the liquid line is controlled according to the temperat-
ure. The capacity of the ECOLITE condensing unit con-
tinues to be controlled according to the suction pres-
sure. The suction pressure set point must therefore be
set to a sufficiently low value.
The external cold store temperature sensor is connec-
ted to the terminal strip X10 terminals 7 and 8. In deliv-
ery condition of the condensing unit, the suction gas
Menu item
F2+F4⇒PAR⇒CPr⇒SP1
Modbus: 16388
F2+F4⇒PAR⇒CPr⇒bHO
Modbus: 16389
F2+F4⇒PAR⇒CPr⇒bH
Modbus: 16390
F2+F4⇒PAR⇒CPr⇒bL
Modbus: 16391
F2+F4⇒PAR⇒CPr⇒bLO
Modbus: 16392
F2+F4⇒PAR⇒CPr⇒OS1
Modbus: 16393
F2+F4⇒PAR⇒CPr⇒CrE
Modbus: 16394
F2+F4⇒PAR⇒CPr⇒tAC
Modbus: 16395
F2+F4⇒PAR⇒CPr⇒tdC
Modbus: 16397
F2+F4⇒PAR⇒CPr⇒OFC
Modbus: 16399
F2+F4⇒PAR⇒CPr⇒OnC
KB-206-1
Function
Set point of suction pressure regulator
-45.0 – 22.5°C
Setting ex factory: -10.0 °C
Width of upper neutral band with 2 suction pressure regulators
0.0 – 20.0 K
Setting ex factory: 5.0 K
Width of upper neutral band with 1 suction pressure regulator
0.0 – 20.0 K
Setting ex factory: 2.0 K
Width of lower neutral band with 1 suction pressure regulator
0.0 – 20.0 K
Setting ex factory: 2.0 K
Width of lower neutral band with 2 suction pressure regulators
0.0 – 20.0 K
Setting ex factory: 5.0 K
Set point adjustment of suction pressure set point via digital input
-50.0 – 50.0 K
Setting ex factory: 5.0 K
Duration CR II valve(s) closed until compressor is shut off
0 – 120 s
Setting ex factory: 60 s
Delay in change of upper neutral band
0 – 120 s
Setting ex factory: 10 s
Delay in change of lower neutral band
0 – 120 s
Setting ex factory: 10 s
Minimum duration compressor stop ⇒ compressor start
0 – 1200 s
Setting ex factory: 60 s
Minimum duration compressor start ⇒ compressor start
temperature sensor is connected to these terminals.
This sensor must be disconnected when the cold store
temperature sensor is connected and is therefore not
operational when the cold store temperature control is
active. BITZER cold store temperature sensors (NTC,
10kΩ@25°C) should be used. Other sensors are not
supported.
Compressor and CR II capacity regulator control –
menu CPr:
23