Mounting; Transporting The Condensing Unit; Transport Locks For Condensing Units; Installing The Condensing Unit - Bitzer LHL3E/2EES-2Y Instructions De Service

Masquer les pouces Voir aussi pour LHL3E/2EES-2Y:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6 Mounting

6.1 Transporting the condensing unit

Fix either screw-in eyes or rails with screws on the four
load suspension points. The screw-in eyes and screws
must not exceed a maximum screw-in thread length of
30 mm because otherwise the condenser may become
damaged! Screw-in eyes, screws and rails are not in-
cluded in the scope of delivery.
Lift the condensing unit either by means of the lifting
slings by crane or forklift or by hand directly on the
rails.
Fig. 2: Load suspension points M8x30 (max.)
Fig. 3: Transport rail
KB-206-1
Fig. 4: Lifting on lifting slings by forklift or crane
Fig. 5: Lifting on transport rail by hand
6.1.1

Transport locks for condensing units

To avoid transport damage to condensing units in their
state of delivery, the vibration dampers of the com-
pressors are blocked by transport locks. It is absolutely
necessary to remove or loosen these locks after mount-
ing. For this, see the operating instructions of the com-
pressor KB-104.

6.2 Installing the condensing unit

The place of installation must have sufficient load-car-
rying capacity and must be level and vibration-resistant.
The minimum distances to fixed delimiting surfaces
must be complied with. Avoid a short-circuit of the air
flow or obstacles in the air flow of the condenser fans!
During the system design, take the minimum and max-
imum load into account. Execute the pipe works and
rising lines according to the generally known rules for
compound systems. Contact BITZER if the system is
M8x30 (max.)