MarelliMotori D-Vo Light Manuel D'utilisation page 26

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

The following table specifies the state contact usage logic for the excitation start/stop modes and the operating
modes.
DIGITAL INPUT SETUP / OPERATING MODE SELECTION
INPUT
DIGITAL INPUTS
Associated contact
Stand-by
Excitation start in AVR
mode
START/STOP
(SOFT START)
MODE
Excitation
stop
Stand-by after a STOP,
to perform
a new START
AVR mode
In stand-alone operation
Voltage matching
OPERATING
MODES
Droop
Grid parallel (PF/VAR)
FCR
(1) It depends on the state of the field Enable voltage setpoint adjustment in the D-Vo Dashboard tab Droop
compensation (Paragraph 7.3.4): if not enabled, state must be = 0; if enabled, state = X.
(2) The PF mode or the VAR mode can be selected through the D-Vo Dashboard tab Generator data / Options
(Par. 7.3.4).
LEGEND
0
CONTACT OPEN
1
CONTACT CLOSED
X
NOT RELEVANT
NOTE: if the auxiliary power supply is missing, the STOP state information is lost; as a consequence, the START
and STOP management described above only applies when the D-Vo is running under one of the following
operating conditions:
1. separate power and auxiliary supply, i.e. auxiliary supply always on even when the generator is stopped;
2. auxiliary supply shunted from power supply and generator running at full rpm (with residual auxiliary supply
>20Vac).
9638571A0_C
START
STOP
C1
C2
(Default)
(Default)
(Default)
0
X
1
0
1
1 (pulse)
0
0
1
0
1
0
1
0
0 - X
1
0
1
0
1
0
D-Vo Light – Marelli Motori
PAR
PF/VAR
VMATCH
C5
C6
C7
(Default)
(Default)
X
X
X
0
X
X
X
X
X
0
0
0
(1)
0
1
0
(2)
0
1
X
X
FCR
C8
(Default)
X
X
X
0
X
X
X
X
X
0
0
0
1
0
X
0
0
0
X
1
EN
26

Publicité

Table des Matières
loading

Table des Matières