6.6.3 Test Mode Evaluation, Service und Check-1094
First the maximum Vapor flow is established. After this the simulation of the fuel
flow starts. It begins with 40 l/min is changed by pressing the keys
The simulated fuel flow is displayed in the upper right corner.
Input
Display (2-lines)
V4.1
INIT
Fuel flow
ENTER
ACT.
Vapor flow Max
DATA
TEST
Vapor flow 40
DATA
TEST
C-factor
TEST
Recovery rate 40
TEST
Corr. VR
TEST
Vapor flow 40
DATA
ACT.
Operating Instructions No. 893 193
Selection
Operator?
CHECK-1094
40,0
l/min
46,0
l/min
44,0
l/min
40
110
%
110
%
40
100
%
44,0
l/min
Remark
Selecting the operator mode
Display mode
Vapor flow
Vapor flow
Correction factor
Recovery rate
Correct Recovery rate
Return to display mode