Note: If no selection is confirmed within 3 s, the software automatically returns to normal operating mode.
5.5 Alarms
In the event of alarms, the red LED flashes, the alarm relay closes, activating the remote signal (if installed) and the alarm code flashes on the
display.
There are two types of alarms: warnings and shutdown alarms. The former can be deleted by pressing the "reset/sel" button for 2 s, while the latter
are displayed until maintenance is performed. Multiple alarms flash in sequence, alternating with the main display.
The table below (Tab. 5.a) shows all the alarm codes, with a description of the problems that cause these and the actions required to restore
normal operation.
Display
Description
Remote ON/OFF open
- -
Internal memory error
EE
Control board configuration not valid Unit disabled
E0
High current alarm
E1
Low production, low conductivity of
E2
the supply water or excessive foam/
lime scale in the cylinder
E3
Cylinder almost depleted
E4
Fill alarm, water not filling or fill too
slow (the current does not increase
within the set time)
E5
Drain alarm, cannot perform the drain
(the current does not decrease within
the set time)
E7
Foam detected
Cylinder lifetime expired (3000 hours) Unit Disabled: Reset the hour
E8
E9
High temperature of the control
device (above 80°C / 176°F)
"compactsteam" +03U0092EF - rel. 1.0 - 2020.08.31
Action
Unit disabled
Contact the service centre
Unit disabled
Unit disabled.
Press the "reset/sel" button for 1
second to delete the alarm
Not resettable: the unit contin-
ues producing steam; the warn-
ing is automatically reset only
when the humidifier is able to
reach the required steam pro-
duction in kg/h
Press the "reset/sel" button for
1 second to delete the alarm;
otherwise, the signal will be
automatically reset every 10
minutes until the supply water
is available again.
Press the "reset/sel" button for 1
second to delete the alarm
Press the "reset/sel" button for 1
second to delete the alarm
counter (read chap. Resetting
the hour counter")
The signal is automatically reset
if the temperature falls below 80
°C / 176 °F.
28
Red
Alarm
LED
relay
OFF
OFF
Jumper terminals AB-AB
ON
ON
This should never occur in the field; have
the appliance reprogrammed by the
service centre
ON
ON
This should never occur in the field; have
the appliance reprogrammed by the
service centre.
ON
ON
1) Turn off;
2) Check the connections;
3) Check the cylinder (no bridges of
lime scale between the electrodes);
4) Check that the electrodes are not
shorted.
ON
ON
Check the conductivity of the supply water
and if necessary replace the cylinder with
the low conductivity version.
Off
Off
Change cylinder (if necessary).
ON
ON
1) Check the water supply and the fill
valve;
2) Check for any leaks from the drain
pump;
3) Make sure the filter on the fill solenoid
valve is not blocked (Fig. 3.g);
4) Check that the steam outlet is not
wor king against excessive backpres
sure, preventing the flow of water
into the cylinder by gravity;
5) Check that the steam outlet hose
is not choked or that there are no
pockets of condensate;
6) Check that the power cables are
connected to the cylinder.
1) Make sure the drain pump is not
ON
ON
blocked
2) Check that there are no blockages in
the drain connection.
If the problem persists, perform a number
OFF
OFF
of cleaning cycles (see chapter 4.4 "Start-
ing with a new cylinder")
Change the cylinder
On
On
Replace the control device
OFF
OFF
Notes
Tab. 5.a