Steam cylinder hose adapter
Fig. 3.j
Steam hose
• make the connection between the humidifier and distributor
using a hose (it is recommended to use the steam hoses
supplied by CAREL code SHOSE0022). Unsuitable hoses may
weaken and crack causing steam leaks;
• avoid the formation of pockets or traps where condensate may
form;
• avoid choking the hose due to tight bends or twisting.
fasten the end of the hose to the connectors on the humidifier
and the steam distributor using metal clamps (not supplied), so
that these do not detach due to the high temperature.
To connect to the cylinder hose steam use the adapter code
CHKADAP000.
WARNING: the length of the hose must not exceed 4 m / 13ft.
Figure 3.k shows examples of correct and incorrect installation of
the steam delivery hoses and condensate drain hoses.
19
"compactsteam" +03U0092EF - rel. 1.0 - 2020.08.31
ENG