Upright Steam Flow-Rate; Steam Flow-Rate, Sab/Sat Versions; Steam Flow-Rate, Sa0 (Single-Pipe) Versions - Carel ultimateSAM Mode D'emploi

Masquer les pouces Voir aussi pour ultimateSAM:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

SAKD0S2000 kit:
(center distance 420mm(16.5in))
Effective single upright flow-rate ≤ 50kg/h (110lb/h)
H=150mm (5.9in) L=420mm (16.5in)
Minimum AHU height: 720mm (28.3in)
Effective single upright flow-rate > 50kg/h (110lb/h)
H=200mm (7.9in) L=420mm (16.5in)
Minimum AHU height: 820mm (32.3in)
H
L
L
250 mm
SAKD0S2000 kit:
(center distance 420mm(16.5in))
Effective single upright flow-rate ≤ 50kg/h (110lb/h)
H=150mm (5.9in) L=420mm (16.5in)
Minimum height: 820mm (32.3in)
Effective single upright flow-rate > 50kg/h (110lb/h)
H=200mm (7.9in) L=420mm (16.5in)
Minimum height: 870mm (34.3in)
For steam flow-rates less than or equal to 50kg/h (for single upright):
H = 150 mm; U = 160 mm;
For steam flow-rates starting from 50kg/h (excluded) (for single upright):
H = 200 mm; U = 200 mm.
Leave at least 25 mm (1") free space between the device and the wall of
the duct.

1.8 Upright steam flow-rate

The uprights on the ultimateSAM come in two different diameters. In the
"S" configuration (6th digit of the ultimateSAM code) the diameter of the
uprights is 35 mm ( 1.37"), to increase flow-rate on single uprights there is
also the "L" configuration (6th digit of the ultimateSAM code) in which the
diameter of the uprights is 45 mm ( 1.77").
1.8.1

Steam flow-rate, SAB/SAT versions

For ultimateSAM multi-upright models (SAB/SAT), the maximum steam
flow-rate for each upright also depends on the configuration of the
ultimateSAM. In fact, with top feed the upright steam flow-rate increases as
condensate flows in the same direction as draining. Below are the flow-rates
for the two versions.
Upright configuration
Upright diameter
Maximum single upright flow-rate in
the ultimateSAM SAB* configuration
Maximum single upright flow-rate in
the ultimateSAM SAT* configuration
1.8.2

Steam flow-rate, SA0 (single-pipe) versions

For ultimateSAM SA0 (single-pipe) versions, the flow-rate of the distribution
tube depends on the application being developed. At atmospheric pressure,
i.e. when the distributor is supplied by a steam humidifier, 50 kg/h (110 lbs/
hr) is the maximum steam flow-rate (maximum 20 kg/h (44 lbs/hr) for codes
SA0AA***** and SA0BA*****). This physical limit relates to the backpressure
that would be generated in the steam humidifier located upstream of the
ultimateSAM SA0 distributor.
If the steam inlet is pressurized (pressure higher than 0 bars: 0,1...4bar (1.45-
58 psi), the maximum load allowed for each upright increases with the
length of the SA0 upright (see the table below for the flow-rates).
Table of steam flow-rates for ultimateSAM SA0 versions:
code
Upright
Maximum steam
length mm
flow-rate at atmo-
(in)
spheric pressure
(SA0 supplied by
steam humidifier)
SA0AALI0*0
358 (14.1)
SA0BALI0*0
510 (20.1)
SA0CALI0*0
662 (26.1)
SA0DALI0*0
814 (32.0)
SA0EALI0*0
966 (38.0)
SA0FALI0*0
1118 (44.0)
SA0GALI0*0
1270 (50.0)
SA0HALI0*0
1422 (56.0)
SA0IALI0*0
1574 (62.0)
SA0JALI0*0
1726 (68.0)
SA0KALI0*0
1878 (73.9)
SA0LALI0*0
2030 (79.9)
13
"ultimateSAM - user" +03U0070EF - rel. 2.0 - 20150301
ENG
Type "S"
Type "L"
35 mm (1.37")
45 mm (1.77")
(22 lbs/hr)
(37 lbs/hr)
10 kg/h
16.7 kg/h
(66 lbs/hr)
(110 lbs/hr)
30 kg/h
50 kg/h
Maximum
Minimum
steam flow-rate
width of the
with pressurized
duct mm
steam
(inches)
0,1...4bar
kg/h (lbs/hr)
(1.45-58 psi)
kg/h (lbs/hr)
20 (44)
20 (44)
383 (15.1)
20 (44)
30 (66)
535 (21.1)
50 (110)
50 (110)
687 (27.0)
50 (110)
60 (132)
839 (33.0)
50 (110)
70 (154)
991 (39.0)
50 (110)
80 (176)
1143 (45.0)
50 (110)
90 (198)
1295 (51.0)
50 (110)
100 (220)
1447 (57.0)
50 (110)
110 (242)
1599 (63.0)
50 (110)
120 (264)
1751 (68.9)
50 (110)
130 (286)
1903 (74.9)
50 (110)
140 (308)
2055 (80.9)
Tab. 1.e
Tab. 1.f

Publicité

Chapitres

Table des Matières
loading

Table des Matières