C1: Phase Current Display; Multi-Pump System - DAB esybox max 85/120 Instructions Pour L'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 73
8.1.2 RS: Rotation speed display
Motor rotation speed in rpm.
8.1.3 VP: Pressure display
Plant pressure measured in [bar] or [psi] depending on the measuring system used.
8.1.4 VF: Flow display
Displays the instantaneous flow in [litre/min] or [gal/min] depending on the set measuring system.
8.1.5 PO: Absorbed power display
Power absorbed by the electropump in [kW].
A flashing round symbol may appear under the symbol of the measured power PO. This symbol indicates the pre-alarm for exceeding the
allowed maximum power.

8.1.6 C1: Phase current display

Motor phase current in [A].
A flashing round symbol may appear under the symbol of the phase current C1. This symbol indicates the pre-alarm for exceeding the allowed
maximum current. If it flashes at regular intervals it means that the motor overload protection is about to trip and it will very probably go into
protection status.
8.1.1 TE: Heat sink temperature
Heat sink temperature display
8.1.2 Pin: Pressure at intake
Pressure at intake measured in [bar] or [psi] depending on the measuring system used.
8.1.3 Operating hours and number of starts
Indicates on three lines the hours that the device has been powered up, the pump working hours and the number of starts of the motor.
8.1.4 PI: Power histogram
A histogram of the power delivered is displayed on 5 vertical bars. The histogram indicates how long the pump has been on at a given power
level. On the horizontal axis are the bars at the various power levels; on the vertical axis, the time for which the pump has been on at the
specific power level (% of the time with respect to the total).
8.1.5

Multi-pump system

Displays the system status when in the presence of a multi-pump installation. If communication is not present, an icon depicting communication
absent or interrupted is displayed. If there are several devices connected to one another, an icon is shown for each of them. The icon has the
symbol of a pump under which are characters indicating the pump status.
Depending on the operating status it will display as in Table 8.
Status
Motor running
Motor stopped
Device faulty
If the device is configured as reserve the icon depicting the pump is dark in colour, the display remains similar to Table 5 with the exception that,
if the motor is stopped, it shows F instead of SB.
ENGLISH
Figure 15 Power histogram display
System display
Icon
Symbol of pump turning
Symbol of static pump
Symbol of static pump
Table 8 View of the multi-pump system
51
Status information under the icon
Speed in three figures
SB
F

Publicité

Table des Matières
loading

Table des Matières