Fluidinstallation
8.2.
Installing the process valve
Thread type and dimensions can be found in the corresponding data
sheet.
Connect the valve according to the operating instructions for the
valve.
8.3.
Pneumatic connection of the
Pneumatic Control Unit
DANGER!
Risk of injury from high pressure in the equipment/device.
▶ Before working on equipment or device, switch off the pressure
and deaerate/drain lines.
Procedure:
Connect the control medium to the pilot air port (1)
(3 to 7 bar, oil, water and dust-free instrument air).
Attach the exhaust airline or a silencer to the exhaust air port (3).
Important information for the problem-free functioning of the
device:
▶ The installation must not cause back pressure to build up.
▶ Select a hose for the connection with an adequate cross-section.
▶ The exhaust air line must be designed in such a way that no water
or other liquid can get into the device through the exhaust air port.
Type 8697
Fig. 17: Pneumatic connection
Caution: (Exhaust air concept):
In compliance with degree of protection IP67, an exhaust air
line must be installed in the dry area.
Keep the adjacent supply pressure always at least 0.5 – 1
bar above the pressure which is required to move the actuator
to its end position.
english
Pilot air port
label: 1
Exhaust air port
label: 3
21