Fluid Installation
7.2.
installing the process Valve
Thread type and dimensions can be found in the corresponding data
sheet.
7.3.
pneumatic connection of the
pneumatic control unit
Danger!
danger – high pressure in the equipment!
Before loosening the lines and valves, turn off the pressure and
vent the lines.
procedure:
Connect the control medium to the pressure supply connection (1)
(3 to 7 bar, oil, water and dust-free instrument air).
Attach the exhaust airline or a silencer to the exhaust air con-
nection (3).
Important information for the problem-free functioning of the
device:
The installation must not cause back pressure to build up.
Select a hose for the connection with an adequate cross-section.
The exhaust air line must be designed in such a way that no water
or other liquid can get into the device through the exhaust air
connection.
Type 8690
Fig. 17:
Pneumatic connection
Caution: (Exhaust air concept):
In compliance with protection class IP67, an exhaust air line
must be installed in the dry area.
Keep the adjacent supply pressure always at least 0.5 –
1 bar above the pressure which is required to move the
actuator to its end position.
english
Pressure supply
connection
label: 1
Exhaust air
connection
label: 3
21