NOTE!
Too high torque when screwing in the fastening screw does
not ensure degree of protection IP65 / IP67.
▶ The fastening screws may be tightened to a maximum torque of
0.5 Nm only.
Attach the Pneumatic Control Unit to the actuator using the two
side fastening screws. In doing so, tighten the fastening screws
hand-tight only (maximum torque: 0.5 Nm).
3. Installation of the pneumatic connection on the actuator
Pilot air outlet 2
Pilot air outlet 2
Upper pilot air port
Lower pilot air port
Fig. 13: Installation of the pneumatic connection, 20xx series
Type 8697
Installation
1
2
Screw the plug-in hose connectors onto the Pneumatic Control
Unit and the actuator.
Using the hoses supplied in the accessory kit, make the connection
between the Pneumatic Control Unit and the actuator with the fol-
lowing "Tab. 1: Pneumatic connection to actuator".
NOTE!
Damage or malfunction due to ingress of dirt and moisture.
▶ To comply with degree of protection IP65 / IP67, connect the
pilot air outlet which is not required to the free pilot air port of the
actuator or seal with a plug.
"In rest position" means that the pilot valves of the Pneumatic
Control Unit Type 8697 are isolated or not actuated.
If the ambient air is humid, a hose can be connected between
pilot air outlet 2
of the Pneumatic Control Unit and the
2
unconnected pilot air port of the actuator for control function
A or control function B. As a result, the spring chamber of
the actuator is supplied with dry air from the vent duct of the
Pneumatic Control Unit.