Figure 14: Position of the anchoring points (screws and
wall plugs)
5.4 Mounting the Inverter
Risk of injury due to weight of product
Injuries may result if the product is lifted incorrectly
or dropped while being transported or mounted.
• Transport and lift the product carefully. Take
the weight of the product into account.
• Wear suitable personal protective equipment
for all work on the product.
Procedure:
1. Attach M12 eyebolts and matching nuts to the
inverter (not included in the scope of delivery).
2. Lift the inverter. Only handle the inverter by the
recessed grips on the sides.
Figure 15: Figure 2.11 Lifting the inverter
Installation Guide
3. Locate the slots on the side of the wall mounting
bracket.
Figure 16: Hooking the inverter into the wall mounting
bracket
4. On the inverter, position the side screws against
the wall mounting bracket slots. Insert the screws
into the two lower slots and into the upper slots.
5. Ensure that the four side screws sit securely in the
wall mounting bracket slots.
6. Remove eyebolts and keep for disassembly.
5.5 Disassembly
Procedure:
1. Attach M12 eyebolts and matching nuts to the
inverter (not included in the scope of delivery).
2. Lift and slide the inverter out of the wall mounting
bracket slots.
3. Lift the inverter off the wall mounting bracket.
4. Remove eyebolts
SHP75-10-STP60-10-IA-xx-20
5 Installation