SMA SUNNY HIGHPOWER PEAK1 Instructions D'installation page 48

Masquer les pouces Voir aussi pour SUNNY HIGHPOWER PEAK1:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

9 Technical Data
Parameters
Pollution Degree
Environmental category IEC62109-1
Environmental class in accordance with IEC
60721-3-4
Cooling concept
Air quality - general
Air quality - coastal, heavy industrial and agricultural
zones
Vibration
Enclosure protection class
UL 50E enclosure type
Maximum operating altitude above mean sea level
Installation
* Potential power reduction above 45°C (for further information see technical information "Efficiencies and Derating")
** Installation at altitudes > 2000 m are possible on request; contact SMA Solar Technology AG for this.
48
SHP75-10-STP60-10-IA-xx-20
Specification
PD2
Outdoor, wet (details (see Section 5.2, page 22))
4K4H/4Z4/4B2/4S3/4M2/4C2
Forced air cooling
ISA S71.04-1985
Class G3 (at 75% rF)
Must be measured and classified in accordance with
ISA S71.04-1985: G3 (at 75% RH)
< 1 G
IP65
NEMA 3R
2000 m above sea level (power reductions may
occur starting at an altitude of 1000 m).**
Avoid constant contact with water.
Avoid direct solar irradiation.
Ensure adequate air flow.
Mount on non-flammable surface.
Mount upright on vertical surface.
Prevent dust and ammonia gases.