Mounting The Inverter - SMA SUNNY BOY STORAGE 3.8-US Instructions D'installation

Masquer les pouces Voir aussi pour SUNNY BOY STORAGE 3.8-US:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

SMA Solar Technology AG
Prescribed clearances in accordance with the National Electrical Code
Canadian Electrical Code
Under certain conditions, the National Electrical Code
CSA C22.1 specify greater clearances.
• Ensure that the prescribed clearances in accordance with the National Electrical Code
or Canadian Electrical Code
☐ Maintain the recommended clearances to walls as well as to other inverters or objects.
☐ If multiple inverters are mounted in areas with high ambient temperatures, increase the
clearances between the inverters and ensure sufficient fresh-air supply.
550
(21.64)
Figure 9 : Recommended clearances(Dimensions in mm (in))
5.2

Mounting the Inverter

Additionally required mounting material (not included in the scope of delivery):
☐ Three screws suitable for the support surface (diameter: 8 mm (5/16 in))
☐ Three washers suitable for the screws
☐ Where necessary, 3 screw anchors suitable for the support surface and the screws
☐ To secure the inverter against theft: one padlock suitable for outdoor use
☐ Padlock dimensions:
– Diameter of the shackle: 8 mm to 10 mm (0.31 in to 0.39 in)
– Width of the shackle (inner dimension): 30 mm to 40 mm (1.18 in to 1.57 in)
– Height of the shackle (inner dimension): 30 mm to 40 mm (1.18 in to 1.57 in)
Installation Manual
®
CSA C22.1
®
CSA C22.1 are adhered to.
500
(19.69)
®
or the Canadian Electrical Code
550
(21.64)
SBSxx-US-10-IA-xx-12
5 Mounting
®
or
®
®
27