Opening the installation area with two-piece
enclosure lid:
1. Disconnect the inverter.
2. Loosen the three front screws (TX30) on the cover
of the installation area. The screws are captive
screws and cannot fall out.
3. Raise the cover by 180 degrees. A magnet
enables the cover to stay open.
Figure 17: Loosen front screws and lift the cover
4. To close the cover, lower it into place and fasten
the three front screws.
5.7 Enclosure Opening
The mounting brackets for the cable glands are
already pre-mounted.
Figure 18: AC cable gland
Installation Guide
Figure 19: DC cable gland
Device Type
Terminal Range
SHP 75-10
AC+PE
DC (PV)
STP 60-10
AC+PE
DC (PV)
1)
Observe the ampacity of cables used.
Device Type
Conductor material
SHP 75-10
Al/Cu
Al/Cu
STP 60-10
Al/Cu
Al/Cu
Device Type
Cable sheath diameter with
supplied cable gland
SHP 75-10
46 to 53 mm
18 to 25 mm
STP 60-10
37 to 44 mm
14 to 21 mm
SHP75-10-STP60-10-IA-xx-20
5 Installation
1)
35 to 150 mm²
35 to 150 mm²
16 to 95 mm²
16 to 95 mm²