6.2 Protections
The Relay Driver is fully protected against system faults listed below.
Recovery is automatic for short circuits. Channel overloads are current-
limited. Refer to section 6.1 for fault LED indications.
Reverse polarity – Relay Driver power
Reverse polarity – Channel input voltage, all 4 channels
Short circuit and overload – all 4 channels
6.3 Maintenance
The Relay Driver is designed to run automatically without the need for
user intervention. However, the operator should perform the following
tasks annually to ensure continued operation:
 Verify that the LEDs indicate normal operation.
 Tighten all terminal connections. Check for corrosion or loose
connections
 Check the Relay Driver power source. Verify that the source voltage is
within the recommended voltage window (8 – 68Vdc)
 Inspect the communications cables for loose connections (if applicable)
 Inspect for signs of nesting insects