EN
For correct installation, please observe the flue sections/lengths indicated in the technical
data table. For installations of other dimensions, the flue must be correctly sized in
accordance with standard EN13384-1.
The draught created by your flue must be sufficient but not excessive.
If the flue cross-section is too large, the volume of flue gas may be too large for the appliance to
heat, causing operating difficulties, to avoid this, the appliance must be intubated over its entire
height. If the cross-section is too small, the draught will be reduced.
ATTENTION: with regard to the construction of the flue connection and flammable materials,
please follow the requirements provided. The flue pipe must be at an appropriate distance from
flammable or combustible materials, using suitable insulation or an air gap.
It is FORBIDDEN to run the system's pipework or air ducts inside the flue. It is also forbidden to
create mobile or fixed openings on the flue itself, for the connection of other different appliances.