PARAMETERS FOR AVAILABLE
EN
OUTPUTS PROGRAMMING
Para-
Function
meter
F1.15 SWITCH- OFF
DIFFERENCE FOR
DIFFERENTIAL
THERMOSTAT
F1.16 CIRCULATION ON
OUTPUT
F1.17 SWITCH-ON
IMPULSE /
CIRCULATION
PUMP RUNNING
TIME
F1.18 SWITCH-ON
DELAY /
CIRCULATION
PUMP STANDBY
TIME
* Depends on the controller model.
|
40
Setting range
Switch -off difference setting for
differential thermostat.
Selection if output should be used for hot
water circulation and the way it should
operate.
1- circulation with pump running and
standby time
2- circulation is activated with flow switch
on terminal T3 and is running for setted
running time
3- circulation is activated with flow switch
on terminal T4 and is running for setted
running time
4- circulation is activated with flow switch
on terminal T5 and is running for setted
running time
5- circulation is activated with flow switch
on terminal T6 and is running for setted
running time
This function activates output for setted
time. After setted time expires, the output
is switched off, regardless to other switch-
on or switch-off commands.
This setting is especially useful for control
of support pump in Drain-back systems.
Setting 0 means there is no delay and
the output should activate immedately
and stay activated for the whole time of
switch-on command.
This function delays activation of output
for setted time. Output is activated when
setted delay time expires.
REMARK: If delay time is longer as time of
switch-on period the output won't activate.
Setting 0 means there is no delay and
the output should activate immedately
and stay activated for the whole time of
switch-on command.
Default value
Default
value
1 ÷ 20 °C
3
0- NO
0*
1- YES, RUN/
STANDBY TIME
2- YES, T3
3- YES, T4
4- YES, T5
5- YES, T6
0 ÷ 3600 s
0
0 ÷ 3600 s
0
Service settings manual