HEAT METERING PARAMETERS
Group W contains parameters to set the solar heat metering.
The procedure for setting function parameters is the same as for service parameters.
TABLE WITH DESCRIPTION OF PARAMETERS
Para-
Function
meter
W1.1
HEAT METERING With this setting we turn on the
W1.2 MEDIUM
W1.3 GLYCOL
MIXTURE
W1.4 HOT SENSOR
W1.5 COLD SENSOR
W1.6 FLOW METER
W1.7 IMPULSE RATE
OF FLOW
METER
W1.8 FLOW IN FIRST
COLLECTOR
FIELD
W1.9 FLOW IN
SECOND
COLLECTOR
FIELD
W1.10 FLOW IN FIRST
AND SECOND
COLLECTOR
FIELD
Service settings manual
Setting range
system which measures acquired solar
energy.
Select transfer medium in the solar
system.
Set the glycol concentration.
By Tyfocor LS and G-LS this setting
has no effect.
Select the sensor which is in
collectors.
Select the sensor Tc which is on the
return pipe into collectors.
With settings you define whether
there is a built-in flow meter.
You insert characteristic data of
flow meter - amount od volume per
impulse.
If you do not use the flow meter, read
out and set flow from the mechanic
flow meter in first collector field when
the pump is running at 100 %.
If you do not use the flow meter, read
out and set flow from the mechanic
flow meter in second collector field
when the pump is running at 100 %.
If you do not use the flow meter, read
out and set flow from the mechanic
flow meter for both collector fields
when both pumps are running at 100
%. This setting is used only by schems
where both collector fields can oper-
ate simultaneously.
Default value
0- NO
1- YES
0- WATER
1- PROPYLENGLYCOL
2- ETHYLENGLYCOL
3- TYFOCOR
4- TYFOCOR LS, G-LS
5- THESOL
10 ÷ 100 %
1- T1 (T3)
2- T2
3- T3
4- T4
5- T5
6- T6
1- T1
2- T2
3- T3
4- T4
5- T5
6- T6
0- NO
1- IMPULSE
0,5 ÷ 25 l/imp
1 ÷ 100 l/min
1 ÷ 100 l/min
2 ÷ 100 l/min
EN
Default
value
0
0
40
1
7
0
1
6
6
12
|
35