TABLE WITH DESCRIPTION OF PARAMETERS:
Para-
Function
meter
S1.1
HYDRAULIC SCHEME Selection of hydraulic scheme.
S1.2
CODE FOR
UNLOCKING THE
SERVICE SETTINGS
S1.4
TEMPERATURE
ROUND UP
S1.5
PERIOD OF
TEMPERAT.
LOGGING
S1.6
ADVANCED DISPLAY
OF TEMPERATURES
S1.7
AUT. SHIFT OF
CLOCK TO SUMMER
/ WINTER TIME
ANTI-BLOCK
S1.8
FUNCTION
INVERTED
S1.9
OPERATION OF
OUTPUTS
S1.10
TONES
S1.13
SENSOR T1
CALIBRATION
S1.14
SENSOR T2
CALIBRATION
S1.15
SENSOR T3
CALIBRATION
Service settings manual
SERVICE PARAMETERS
Setting range
This setting enables the change of code
which is necessary to unlock the service
settings (S and F parameters).
WARNING! Keep new code on a safe
place. Without this code is impossible
to change service settings.
Precision of displayed temperatures.
By setting this field you define how
often the measured temperatures are
saved.
Advanced display of temperatures
displays temperatures on main screen
in double rows. First row is measured
temperature; second row is required or
calculated temperature.
With the help of a calendar, the
controller carries out the automatic
clock changeover between summer and
winter time.
All outputs that haven't been activated
in the last week are activated on Friday
at 20:00 for 60 seconds.
Setting of inverted operation for
outputs. Invertion of output is possible
only if operation mode of output is ON/
OFF (S3.1=0).
By setting this field you define whether
key pressing is accompanied with sound
signals or not.
Correction of displayed measured
temperature for sensor T1.
Correction of displayed measured
temperature for sensor T2.
Correction of displayed measured
temperature for sensor T3.
EN
Default value
Default
value
depends
201
on type of
controller
0000 - 9999
0001
0- 0.1 °C
2
1- 0.2 °C
2- 0.5 °C
3- 1 °C
1 ÷ 30 min
5
0- NO
1
1- YES
0- NO
1
1- YES
0- NO
0
1- YES
0- NO
0
1- R1
2- R2
0- OFF
1
1- KEYPAD
2- ERRORS
3- KEYPAD &
ERRORS
-5 ÷ 5 °C
0
-5 ÷ 5 °C
0
-5 ÷ 5 °C
0
|