5.2.4
Branch Circuit Protection
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes (US) or Canadian Electrical Code, Part 1 (CA).
WARNING - The opening of the branch-circuit protective device may be an indication
that a fault current has been interrupted. To reduce the risk of fire or electric shock,
current-carrying parts and other components of the controller should be examined and
replaced if damaged. If burnout of the current element of an overload relay occurs, the
complete overload relay must be replaced.
ATTENTION - LE DÉCLENCHEMENT DU DISPOSITIF DE PROTECTION DU CIR-
CUIT DE DÉRIVATION PEUT ÊTRE DÛ À UNE COUPURE QUI RÉSULTE D'UN
COURANT DE DÉFAUT. POUR LIMITER LE RISQUE D'INCENDIE OU DE CHOC
ÉLECTRIQUE, EXAMINER LES PIÈCES PORTEUSES DE COURANT ET LES
AUTRES ÉLÉMENTS DU CONTRÔLEUR ET LES REMPLACER S'ILS SONT EN-
DOMMAGÉS. EN CAS DE GRILLAGE DE L'ÉLÉMENT TRAVERSÉ PAR LE COU-
RANT DANS UN RELAIS DE SURCHARGE, LE RELAIS TOUT ENTIER DOIT ÊTRE
REMPLACÉ.
Suitable for use on a circuit capable of delivering not more than 100,000 rms symetric
amperes, @B volts maximum and when protected with class J fuse with the following
ratings:
Devices
0004
0008
0011
Devices
0004
0008
0015
0022
0040
Devices
0015
0022
0040
0055
0075
0110
0150
0185
Étude et configuration des variateurs
1 × 110 – 115 V devices
Non semiconductor fuses (cur-
rents are maximum values
10 A
20 A
30 A
1 × 200 – 240 V devices
Non semiconductor fuses (cur-
rents are maximum values)
6 A
10 A
17.5 A
25 A
40 A
3 × 200 – 240 V devices
Non semiconductor fuses (cur-
rents are maximum values)
15 A
17.5 A
30 A
35 A
45 A
70 A
70 A
80 A
Installation conforme à la norme UL
Max. supply short
Max. line voltage
circuit current
100 kA rms (AC)
Max. supply short
Max. line voltage
circuit current
100 kA rms (AC)
Max. supply short
Max. line voltage
circuit current
100 kA rms (AC)
Manuel produit – MOVITRAC
5
115 V
240 V
240 V
43
®