Warning
number
W255
System clock not set. Set
correct time.
W256
A device is lost. Check
connection.
W257
New device detected. Check
device settings.
W258
Device instance is
duplicated.
W501
SCP has fixed a memory
problem, restored defaults.
W502
Not reporting;
Info may be missing.
50
Message
Manual
Manual
Manual
Manual
Manual
Manual
Type
Cause
On initial startup, the clock
needs to be set. The system
will not operate correctly until it
is.
The SCP has lost
communications with another
device on the network.
You have connected a new
device to the network or
reconnected a disconnected
device.
Two networked devices of the
same type have the same
instance.
The SCP encountered an
internal memory problem upon
startup. To remain operational,
the SCP restored its default
settings.
Set the clock to the correct time.
See "Setting the Time" on page 3–
13.
Check network connection
between the SCP and the device.
Acknowledge the message and
check that the device is properly
configured.
Select a different instance ID on
one of the devices' Setup menu.
Acknowledge the warning and
reset configurable settings if
necessary.
Xanbus System Control Panel (SCP) Owner's Guide
Action