Using the Standby Button
Pressing and holding the Standby Button produces the same
result as disabling "Invert" and "AC Charge" from the System
Settings menu on the SCP. Pressing and holding the Standby
button does not affect MPPT charge controller operation. After
disabling inverting and charging with the Standby button, the
system continues to pass AC input through to the loads.
Pressing and holding the Exit and Standby buttons at the same
time puts the entire XW Pro system (including MPPT charge
controllers) into standby mode. In standby mode, the XW Pro
inverter/chargers stop passing AC input through to the loads, and
"Stb" is displayed on Inverter Information Panel.
After the keypress command to enter standby mode, the Xanbus
AGS (if installed) shuts down the generator if it is running, after a
cool-down cycle.
975-1171-01-01
Warnings and Faults
This section describes how fault and warning messages behave,
and what you should do when they appear. For a complete list of
fault and warning messages specific to the SCP, along with
recommended actions to correct the fault or warning condition,
refer to Chapter 5, "Troubleshooting".
IMPORTANT:
The SCP displays fault and warning messages for all Xanbus-
enabled devices in the system. For information about fault and
warnings for other devices, refer to the Troubleshooting chapter
in the Owner's Guide or Operation Guide for each device.
41