Warning Reference Table
Table 1Warning Reference Table
Warning
number
W250
The value failed to change.
Try again.
W251
Please confirm: Equalization
process.
W252
Please confirm:
Restore default settings.
W254
The value failed to change.
Try again.
975-1171-01-01
Message
Automatic
Manual
Manual
Manual
Type
Cause
A Xanbus-enabled device
rejected the new setting.
A temporary communication
problem stopped the SCP
changing a value that you
entered.
You have enabled Equalization
on the inverter/charger or
charge controller menu.
You have selected the Restore
Defaults command.
The setting you are changing
can only be changed when the
system is in Standby mode.
Action
Check device operation guide and
settings. The setting may be out of
range, the system mode may be
incorrect, or another device setting
is overriding the setting you want
to change.
Try changing the value again.
Press Enter to begin equalizing
batteries or Exit to return to the
previous menu.
Press Enter to restore default
settings or Exit to cancel.
Put the system in Standby mode,
change the setting, then return the
system to Operating mode.