Network Layout
Xanbus-enabled devices are linked with separate lengths of
Xanbus cable, as shown in "Daisy Chain Layout" below.
To ensure communication signal quality, each end of the network
must be terminated. The Xanbus-enabled devices at each end of
the network must have a male terminator inserted into their open
network ports.
If the SCP is the last device on the network, the open port on the
SCP must be terminated.
AC1
kW
Inverting
AC2
A
Charging
!
Event
Equalize
Figure 6 Daisy Chain Layout
975-1171-01-01
Guidelines for Routing Xanbus
Cables
SHOCK HAZARD
Do not route the Xanbus cables in the same conduit or panel as
the AC and DC power cabling.
Failure to follow these instructions can result in death, serious
injury, or equipment damage.
Conext XW SCP
Standby
Event/Warning
WARNING
15